Overview            
	    This
type of current transformer is a fully enclosed structure with epoxy resin
casting insulation. It is suitable for current and electric energy measurement
and relay protection in power lines and equipment with 50Hz and rated voltage
of 10kV and below.
	 
	Technical parameters 
	The product meets the
qualified standards: GB1208-2006 and IEC60044-1
	Rated secondary current:
5A or 1A
	Rated frequency: 50Hz
	Ambient temperature: -5°C~ +40°
	  
	
		
			| 
				 
					Rated current ratio (A) 
				 
			 | 
			
				 
					Accuracy class  
				 
			 | 
			
				 
					Dynamic steady current 
				 
				
					(KA) 
				 
			 | 
			
				 
					Rated insulation level 
				 
				
					(kV) 
				 
			 | 
		
		
			| 
				 
					1000-1200/5  
				 
			 | 
			
				 
					0.2/0.2  
				 
				
					0.2/0.5  
				 
				
					0.2/10P15  
				 
				
					0.5/10P15  
				 
				
					10P15/10P15  
				 
			 | 
			
				 
					15/15  
				 
			 | 
			
				 
					12/42/75  
				 
			 | 
		
		
			| 
				 
					1500/5  
				 
			 | 
			
				 
					20/20  
				 
			 | 
		
		
			| 
				 
					2000-3000/5  
				 
				
					4000-5000/5  
				 
			 | 
			
				 
					30/30  
				 
			 | 
		
	
	  
	2D drawing and installation size